Question 1

During checkout of a newly installed conventional Class B initiating device circuit, each manual station produces an alarm when operated. After the stations are reset, removing both field wires from the control unit leaves the circuit indicating normal. The control unit requires a 4.7-kilohm end-of-line resistor. Where is that resistor most likely connected?

Show answer & explanation

Correct answer: B - Across the circuit terminals inside the control unit.

Question 2

A power-limited fire alarm cable will run exposed on approved supports through a ceiling space used to return environmental air. The same continuous cable also passes through a vertical riser. Which of these fire alarm cable markings is sufficient for both portions under NFPA 70 (2020), assuming conductor size and other application requirements are satisfied?

Show answer & explanation

Correct answer: A - FPLP

Question 3

A 24-V protected-premises fire alarm system has no voice evacuation or generator. Its total standby current is 0.40 A, and its total alarm current is 3.0 A. The listed power supply uses two identical 12-V batteries in series; the charger and enclosure permit every capacity listed below. Using the minimum secondary-power duration and battery-aging correction required by NFPA 72 (2022), select the smallest acceptable battery pair.

Show answer & explanation

Correct answer: A - Two 12-V, 18-Ah batteries.

Question 4

At a hotel, the required fire alarm awakening signal measures 82 dBA at the pillow with the guestroom door closed. Ambient noise does not require a level above 75 dBA. The appliance produces a conventional 3,100-Hz pure tone and is not listed as an equivalent low-frequency awakening signal. Which change corrects the remaining audible-notification deficiency?

Show answer & explanation

Correct answer: C - Use a listed 520-Hz square-wave sounder at the required sound level.

Question 5

Check a proposed two-conductor notification appliance circuit: minimum voltage at the supply terminals is 24.0 V; circuit rating is 1.5 A; and the appliance group at the far end draws 1.0 A in alarm. The one-way cable length is 300 ft, and each conductor has a resistance of 4.0 ohms per 1,000 ft. There are no intermediate loads. The appliances require at least 20.4 V. Which review finding is correct?

Show answer & explanation

Correct answer: C - 21.6 V at the appliances; both current and voltage checks pass.

Domain 2: Maintenance (40-50%)

Question 6

A system smoke detector alarms during its prescribed smoke-entry test. A separate check with the manufacturer's calibrated sensitivity instrument measures 3.7% obscuration per foot; the detector's listed acceptable range is 1.0% to 3.0% per foot. What do the two results show?

Show answer & explanation

Correct answer: D - The detector is less sensitive than permitted, despite its functional response.

Question 7

To investigate a persistent alarm on a conventional initiating circuit, a technician has ruled out fire, coordinated testing, and isolated the cable from the control unit, every device, and the end-of-line resistor. With the cable de-energized, a meter reads 0.6 ohm between the two conductors and over 20 megohms from either conductor to ground. These measurements establish which fault?

Show answer & explanation

Correct answer: B - An unintended connection between the two conductors.

Question 8

During a coordinated sprinkler waterflow test, sustained flow equivalent to one sprinkler of the smallest orifice installed is established at the inspector's test connection. The fire alarm control unit indicates SUPERVISORY after 48 seconds, and the supervising station receives the same signal. Evaluate these results under NFPA 72 (2022).

Show answer & explanation

Correct answer: D - The response time is acceptable, but waterflow must initiate an alarm signal.

Question 9

A building's system-connected smoke detectors are 12 years old. They are undamaged, remain compatible with the control unit, and pass their required functional and sensitivity tests. The manufacturer's instructions specify no fixed replacement age. The owner asks whether the 10-year replacement rule for household smoke alarms requires replacing these detectors now. What is the appropriate recommendation?

Show answer & explanation

Correct answer: A - Continue the required inspection, testing, and maintenance; age alone does not require replacement.

Domain 3: Submittal Preparation and System Layout (1-11%)

Question 10

An approved sequence-of-operations matrix gives these responses: operation of duct detector DD-2 produces a supervisory signal, stops AHU-2, and leaves the occupant notification appliances off. A recorded DD-2 test shows a supervisory message at the panel and supervising station, no horn or strobe operation, and AHU-2 still running. Which entry belongs on the discrepancy list?

Show answer & explanation

Correct answer: C - AHU-2 did not stop as required.